Highly efficient water-to-water heat pumps

afilia water series

The heat pumps of the afilia series from 2G adapt fully automatically and very flexibly to the heat requirements in the building or in the industrial process and deliver a constant temperature.

aifilia water series

Even in single-stage versions, our water-to-water heat pumps can achieve temperature fluctuations of up to 70 K. Two-stage concepts are available for applications with higher temperature fluctuations – including project-specific solutions with flow temperatures from up to 100 °C.

All units are fully assembled, tested, and filled with refrigerant and oil at the factory. At the installation site, they only need to be positioned and connected to the hydraulic and power supply lines.

afilia-water-series plant portfolio

  Heating output COP Power consumption Depression
in/out
Source
in/out
C-80-B-r-6-L 96 2,61 37 60/80 10/5
C-80-B-r-6-2S 140 2,66 53 60/80 10/5
C-80-B-r-6-2L 110 2,61 73 60/80 10/5
C-80hts-B-r-6-L 180 3,54 51 60/80 30/25
C-80hts-B-r-6-2S 276 3,56 78 60/80 30/25

C-80hts-B-r-6-2L

359 3,54 102 60/80 30/25
  Heating output COP Power consumption Depression
in/out
Source
in/out
C-90-B-r-6-L 63 2,29 28 70/90 10/5
C-90-B-r-6-2S 90 2,38 38 70/90 10/5
C-90-B-r-6-2L 125 2,29 55 70/90 10/5
C-90hts-B-r-6-L 174 3,67 48 70/90 40/35
C-90hts-B-r-6-2S 255 3,64 70 70/90 40/35

C-90hts-B-r-6-2L

347 3,67 95 70/90 40/35
  Heating output COP Power consumption Depression
in/out
Source
in/out
C-100-B-sc-8593 280 1,92 146 80/100 20/15
C-100-B-sc-8593 430 2,72 155 80/100 35/30
C-100-B-sc-8593 634 3,89 163 80/100 50/45
C-100-B-sc-95113 608 2,06 295 80/100 20/15
C-100-B-sc-95113 910 2,94 310 80/100 35/30

C-100-B-sc-95113

1.380 4,11 336 80/100 50/45
  Heating output COP Power consumption Depression
in/out
Source
in/out
C-50-S-r-06L 525 4,24 124 35/50 10/5

C-50-S-r-08L

698 4,25 165 35/50 10/5
C-50-S-r-12L 1.046 4,27 245 35/50 10/5
C-50-S-r-16L 1.932 4,28 326 35/50 10/5
C-70-S-r-06 974 5,59 174 50/70 35/30
C-70-S-r-08 1.296 5,60 232 50/70 35/30
C-70-S-r-12 1.943 5,62 346 50/70 35/30
C-70-S-r-16 2.586 5,65 458 50/70 35/30
C-90-S-r-06 495 4,38 113 65/90 40/35
C-90-S-r-08 694 4,38 159 65/90 40/35
C-90-S-r-12 1.041 4,38 238 65/90 40/35
C-90-S-r-16 1.387 4,38

317

65/90 40/35
  Heating output COP Power consumption Depression
in/out
Source
in/out
C-50-G-r-700 796 4,26 187 36/56 10/5

C-50-G-r-1100

1.203 4,31 280 36/56 10/5
C-50-G-r-1400 1.602 4,32 371 36/56 10/5
C-50-G-r-1800 2.996 4,32 462 36/56 10/5
C-95-G-r-350 1.215 5,16 236 65/95 48/43
C-95-G-r-550 1.818 5,18 352 65/95 48/43
C-95-G-r-750 2.435 5,21 468 65/95 48/43
C-95-G-r-950 3.040 5,21 584 65/95 48/43
  Heating output COP Power consumption Depression
in/out
Source
in/out
D-95-SG-r-06-08 607 2,80 217 65/95 10/5

D-95-SG-r-08-350

974 2,86 341 70/90 10/5
D-95-SG-r-16-550 1.562 2,55 613 65/95 3/-2
D-95-SG-r-11-550 2.865 3,68 778 70/90 30/25
D-95-SG-r-18-950 2.492 2,82 884 65/95 6/1

your advantages

A complete package that creates added value

Comprehensive control concepts

Including auxiliary drives (pumps, mixers, data collection for heat source/sink)

Superordinate control

Provided by Master Control

Convenient system management

Via my.2-g.com (monthly reports, operating range monitoring)

Intelligent malfunction prediction

in combination with the 2G AI "I.R.I.S."

Integration of spot market optimization

Flex operation and redispatch through partner

Containerized solutions

in different sizes and variations

download now

2G afilia large scale heat pumps

Heat pumps

WE ARE HAPPY TO HELP YOU

Contact our experts

Whether you need advice or a customized solution – we are here for you.